Difference between revisions of "Using with WinCC Flexible"
From IBHsoftec Wiki English
(Created page with "== WinCC Flexible with the IBHsoftec OPC Server V4.x == When creating a project, first select in the column '''<PLC>''' the protocol '''OPC'''. Then at '''<Connect...") |
(→Convienient creation of OPC Variables with the browsing function :) |
||
(4 intermediate revisions by one other user not shown) | |||
Line 6: | Line 6: | ||
[[Image:OPC_CCFlex_1.jpg|frame|none]] | [[Image:OPC_CCFlex_1.jpg|frame|none]] | ||
− | |||
Line 13: | Line 12: | ||
Here also the server '''IBHSoftec.IBHOPC.DA.1''' needs to be chosen. | Here also the server '''IBHSoftec.IBHOPC.DA.1''' needs to be chosen. | ||
− | |||
[[Image:OPC_CCFlex_2.jpg|frame|none]] | [[Image:OPC_CCFlex_2.jpg|frame|none]] | ||
− | |||
− | |||
Line 40: | Line 36: | ||
[[Image:ProTool6 3.jpg|frame|none]] | [[Image:ProTool6 3.jpg|frame|none]] | ||
− | |||
− | |||
Line 49: | Line 43: | ||
[[Image:OPC_CCFlex_3.jpg|frame|none]] | [[Image:OPC_CCFlex_3.jpg|frame|none]] | ||
− | |||
Line 57: | Line 50: | ||
− | + | [[Image:OPC_CCFlex_6.jpg|frame|none]] | |
− | [[Image: | + |
Latest revision as of 10:37, 4 June 2012
WinCC Flexible with the IBHsoftec OPC Server V4.x
When creating a project, first select in the column <PLC> the protocol OPC. Then at <Connection> also OPC may be chosen.
In the project tree-item <Connections> now the connection has to be given a name, in our sample IBHOPC.
Here also the server IBHSoftec.IBHOPC.DA.1 needs to be chosen.
Create OPC variables manually:
In the column <Address> now the desired variables can be entered:
The notation required for WinCC Flexible consists of :
<Access-Path>.<Item Name>
In our sample : S7_300.M.Anlauf
The <Access-Path> corresponds to the name of the <PLC>, as it is defined with the IBH OPCEditor :
Convienient creation of OPC Variables with the browsing function :
A click on the dropdown in the column <Symbol>opens a window, that permits browsing of the servers address space:
The created OPC Variables now may be used: