Configuration of the [http://www.ibhsoftec.com/IBH-Link-UA-Eng IBH Link UA] with TIA portal
 
Configuration of the [http://www.ibhsoftec.com/IBH-Link-UA-Eng IBH Link UA] with TIA portal
  
==Example==
+
==Description==
  
 
In the following example, the configuration with TIA Portal V13 is shown.
 
In the following example, the configuration with TIA Portal V13 is shown.
Line 73: Line 73:
 
[[Image:IBH_Link_UA_S7_IE.png|731px]]
 
[[Image:IBH_Link_UA_S7_IE.png|731px]]
  
[[Image:IBHLink_UA_IP.png|879px]]
+
[[Image:IBH_Link_UA_IP.png|893px]]
  
 
Now a S7 connection between the OPC Server and the PC station must be established:
 
Now a S7 connection between the OPC Server and the PC station must be established:
Line 100: Line 100:
  
 
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S71200.zip TIA Sample: IBH Link UA S7-1200]'''
 
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S71200.zip TIA Sample: IBH Link UA S7-1200]'''
 +
 +
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S71200_V15.zip TIA V15 Sample: IBH Link UA S7-1200]'''
 +
 +
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S71200_V18.zip TIA V18 Sample: IBH Link UA S7-1200]'''
 +
 +
==TIA Sample: IBH Link UA S7-200 via [http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBH Link S7++]==
 +
Notes about the configuration can be found within the '''ReadMe.txt'''.
 +
 +
'''Download: [http://download.ibhsoftec.com/english/Samples/IBH_Link_UA_S7200_TIA.zip TIA Sample: IBH Link UA S7-200 via IBH Link S7++]'''
 +
 +
S7-200 controlers can be connected via the '''[http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBH Link S7++]''' or the '''[http://www.ibhsoftec.com/IBH-Link-S7-PP-HS-Eng IBH Link S7++ HS]''' to the  IBH Link UA.
 +
 +
 +
Within the IBHNet settings the routing mode must be '''deactivated'''. This mode is available beginning with firmware version 2.142.
 +
 +
[[Image:IBH_Link_S7_No_Routing.png|449px]]
 +
 +
The IBH Link S7++ will be configured as a S7-400 station within NetPro wthin an UR1 Rack(18 slots)<br>
 +
MPI addresses of 2-18 for the S7-200 PLC are possible.<br>
 +
The '''slot''' of the CPU represents the '''MPI''' address.
 +
 +
[[Image:IBH_Link_UA_S7_200_TIA_Network.png|491px]]<br>
 +
 +
The following station must be selected:<br>
 +
 +
MLFB: '''6ES7 412-2EK06-0AB0 V6.0'''<br>
 +
IP Address of the IBHLink S7++
 +
 +
 +
Configuration of the Station within the hardware configurator:<br>
 +
 +
[[Image:IBH_Link_UA_S7_200_TIA_HW_Config.png|755px]]<br>
 +
 +
 +
 +
For the PLC a symbol table and the DB1 has to be created, the OB1 should be deleted.
 +
 +
[[Image:IBH_Link_UA_S7_200_TIA_DB1_Eng.png|889px]]
 +
 +
 +
[[Image:IBH_Link_UA_S7_200_TIA_Variables_Table.png|631px]]
 +
 +
 +
 +
 +
[[Image:IBH_Link_UA_S7_200_OPC_TIA_Symbols.png|853px]]
 +
 +
 +
 +
The further pocedure can be found at '''[https://wiki.ibhsoftec.com/en/IBH_Link_UA:Configuration_with_TIA_Portal Configuration with the TIA Portal]'''
  
 
==TIA Sample: IBH Link UA S7-315-2 DP routet via [http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBH Link S7++]==
 
==TIA Sample: IBH Link UA S7-315-2 DP routet via [http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBH Link S7++]==
  
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S7_315_Routing_TIA.zip TIA Beispiel: IBH Link UA S7-315-2 DP routet via IBH Link S7++]'''
+
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S7_315_Routing_TIA.zip TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++]'''
  
==TIA Sample: IBH Link UA S5 95U via IBH Link S5++==
+
S7-300 and S7-400 controllers which do not have an Ethernet port available can be connected via the '''[http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBH Link S7++]''' or the '''[http://www.ibhsoftec.com/IBH-Link-S7-PP-HS-Eng IBH Link S7++ HS]''' to the  IBH Link UA.
 +
 
 +
Within the IBHNet settings the routing mode must be activated. This mode is available beginning with firmware version 2.142.<br>
 +
 
 +
With projected connections via RFC1006 it is not possible to communicate over unprojected connections any more!<br>
 +
 
 +
The normal IBHNet communication over port 1099 via the IBHNet driver is not influenced from this setting.
 +
 
 +
[[Image:IBHLink_routing.png|463]]<br>
 +
 
 +
 
 +
 
 +
The IBH Link S7++ will be configured as a S7-400 station within the TIA Portal and connected with the bus system (MPI or PROFIBUS)<br>
 +
 
 +
[[Image:IBH_Link_UA_Routing_TIA_Dummy_PLC.png|934px]]<br>
 +
 
 +
The following station must be selected:<br>
 +
MLFB: '''6ES7 412-2EK06-0AB0 V6.0'''<br>
 +
Rack '''0''', Slot '''2'''<br>
 +
MPI/PROFIBUS address of the IBHLink S7++<br>
 +
IP Address of the IBHLink S7++
 +
 
 +
Configuration of the Station within the hardware configurator:<br>
 +
 
 +
[[Image:IBH_Link_UA_Routing_TIA_ IBH_Link_as_Station_HWK.png|930px]]<br>
 +
 
 +
 
 +
 
 +
A routed S7 connection from the OPC Server to the S7 PLC must be set up::
 +
 
 +
[[Image:IBH_Link_UA_Routing_TIA_Properties_S7_Connection.png|851px]]
 +
 
 +
 
 +
 
 +
The further pocedure can be found at '''[https://wiki.ibhsoftec.com/en/IBH_Link_UA:Configuration_with_TIA_Portal Configuration with the TIA Portal]'''
 +
 
 +
==TIA Sample: IBH Link UA S5 95U via [http://www.ibhsoftec.com/IBH-Link-S5-PP-Eng IBH Link S5++]==
  
 
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S5.zip TIA Sample: IBH Link UA S5]'''
 
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S5.zip TIA Sample: IBH Link UA S5]'''
 +
 +
SIMATIC® S5 PLC can be connected to the IBH Link UA via the '''[http://www.ibhsoftec.com/IBH-Link-S5-PP-Eng IBH Link S5++]'''
 +
 +
 +
The IBH Link S5++ will be configured as a S7-300 station.
 +
 +
The following station can be selected:<br>
 +
MLFB: '''6ES7 412-2EK06-0AB0 V6.0'''<br>
 +
Rack '''0''', Slot '''2'''<br>
 +
IP Address of the IBHLink S5++
 +
 +
 +
[[Image:IBH_Link_UA_IBH_Link_TIA_S5_Dummy_PLC.png|731px]]
 +
 +
 +
 +
To make global symbols available as OPC Tags in the IBH Link UA it is necessary to define their names.<br>
 +
If information from data blocks are needed dummy DBs have to be created.
 +
 +
 +
[[Image:IBH_Link_UA_IBH_Link_S5_Variables.png|291px]]
 +
 +
 +
[[Image:IBH_Link_UA_IBH_Link_S5_Variables_Table.png|627px]]
 +
 +
 +
[[Image:IBH_Link_UA_IBH_Link_S5_TIA_OPC_Tags.png|787px]]
 +
 +
 +
 +
The further pocedure can be found at '''[https://wiki.ibhsoftec.com/en/IBH_Link_UA:Configuration_with_TIA_Portal Configuration with TIA Portal]]'''

Latest revision as of 08:12, 14 June 2023

Configuration of the IBH Link UA with TIA portal

Description

In the following example, the configuration with TIA Portal V13 is shown.

The S7-1500 station is connected with the IBH Link UA via Ethernet.

The following addresses were chosen in the example:

IP addresses:

Station Address
IBHLink UA 192.168.10.125
S7-1500 192.168.10.129

Configuration:

A new device will be added (in the sample a S7-1500):

IBH Link UA add device.png

The S7-1500 will be connected with Ethernet Subnet PNIE_1 and the IP address must be set:

IBH Link UA S7 1500 PNIE.png

Full access and access with PUT/GET communication is necessary:

IBH Link UA S7 protection.png

Now a DB can be created:

IBH Link UA S7 add DB.png

The Optimized block access must be deactivated:

IBH Link UA S7 DB properties.png

IBH Link UA S7 DB eng.png

Within OB1 the data word 1 and flag word 1 will be counted in our example:

IBH Link UA S7 OB1 eng.png

Flag word 1 is now listed as standard tag:

IBH Link UA S7 standard tag.png

As next step a Simatic PC Station must be added:

IBH Link UA S7 add pc station.png

After adding an OPC Server in slot 1 and an IE-module in slot 2, the version of the OPC Server must be changed form version V12 to V8:

IBH Link UA S7 change device.png

IBH Link UA S7 device V8.png

Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH Links UA must be entered:

IBH Link UA S7 IE.png

IBH Link UA IP.png

Now a S7 connection between the OPC Server and the PC station must be established:

461.px

Within the properies of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:

IBH Link UA S7 PLC tags.png

IBH Link UA S7 DB tags.png

Now the configuration needs to be downloaded to the PLC:

IBH Link UA S7 dwonload plc.png

and to the IBH Link UA:

IBH Link UA S7 dwonload.png

The configuration is now completed and the tags from the IBH link UA are available .

IBHLink UA OPC Client.png

TIA Sample: IBH Link UA S7-1200

Download: TIA Sample: IBH Link UA S7-1200

Download: TIA V15 Sample: IBH Link UA S7-1200

Download: TIA V18 Sample: IBH Link UA S7-1200

TIA Sample: IBH Link UA S7-200 via IBH Link S7++

Notes about the configuration can be found within the ReadMe.txt.

Download: TIA Sample: IBH Link UA S7-200 via IBH Link S7++

S7-200 controlers can be connected via the IBH Link S7++ or the IBH Link S7++ HS to the IBH Link UA.


Within the IBHNet settings the routing mode must be deactivated. This mode is available beginning with firmware version 2.142.

IBH Link S7 No Routing.png

The IBH Link S7++ will be configured as a S7-400 station within NetPro wthin an UR1 Rack(18 slots)
MPI addresses of 2-18 for the S7-200 PLC are possible.
The slot of the CPU represents the MPI address.

IBH Link UA S7 200 TIA Network.png

The following station must be selected:

MLFB: 6ES7 412-2EK06-0AB0 V6.0
IP Address of the IBHLink S7++


Configuration of the Station within the hardware configurator:

IBH Link UA S7 200 TIA HW Config.png


For the PLC a symbol table and the DB1 has to be created, the OB1 should be deleted.

IBH Link UA S7 200 TIA DB1 Eng.png


IBH Link UA S7 200 TIA Variables Table.png



IBH Link UA S7 200 OPC TIA Symbols.png


The further pocedure can be found at Configuration with the TIA Portal

TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++

Download: TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++

S7-300 and S7-400 controllers which do not have an Ethernet port available can be connected via the IBH Link S7++ or the IBH Link S7++ HS to the IBH Link UA.

Within the IBHNet settings the routing mode must be activated. This mode is available beginning with firmware version 2.142.

With projected connections via RFC1006 it is not possible to communicate over unprojected connections any more!

The normal IBHNet communication over port 1099 via the IBHNet driver is not influenced from this setting.

463


The IBH Link S7++ will be configured as a S7-400 station within the TIA Portal and connected with the bus system (MPI or PROFIBUS)

IBH Link UA Routing TIA Dummy PLC.png

The following station must be selected:
MLFB: 6ES7 412-2EK06-0AB0 V6.0
Rack 0, Slot 2
MPI/PROFIBUS address of the IBHLink S7++
IP Address of the IBHLink S7++

Configuration of the Station within the hardware configurator:

IBH Link UA Routing TIA IBH Link as Station HWK.png


A routed S7 connection from the OPC Server to the S7 PLC must be set up::

IBH Link UA Routing TIA Properties S7 Connection.png


The further pocedure can be found at Configuration with the TIA Portal

TIA Sample: IBH Link UA S5 95U via IBH Link S5++

Download: TIA Sample: IBH Link UA S5

SIMATIC® S5 PLC can be connected to the IBH Link UA via the IBH Link S5++


The IBH Link S5++ will be configured as a S7-300 station.

The following station can be selected:
MLFB: 6ES7 412-2EK06-0AB0 V6.0
Rack 0, Slot 2
IP Address of the IBHLink S5++


IBH Link UA IBH Link TIA S5 Dummy PLC.png


To make global symbols available as OPC Tags in the IBH Link UA it is necessary to define their names.
If information from data blocks are needed dummy DBs have to be created.


IBH Link UA IBH Link S5 Variables.png


IBH Link UA IBH Link S5 Variables Table.png


IBH Link UA IBH Link S5 TIA OPC Tags.png


The further pocedure can be found at Configuration with TIA Portal]