For the Mitsubishi control to be accessible via OPC UA, the '''SLMP''' Connection module must be inserted with the '''GX Works''' configuration software: | |||
[[Image:IBH_Link_UA_Mitsubishi_Ethernet_Port.png|227px]] | [[Image:IBH_Link_UA_Mitsubishi_Ethernet_Port.png|227px]] | ||
| Line 5: | Line 5: | ||
[[Image:IBH_Link_UA_Mitsubishi_External_Device.png|783px]] | [[Image:IBH_Link_UA_Mitsubishi_External_Device.png|783px]] | ||
The settings for '''Opening Method''' must be set to '''Do not Open by Program'''.<br> | |||
Please note that these settings '''Opening Method''' are only available for the iQ-R series (and the older System Q). On the FX5U, these parameters cannot be configured. | |||
[[Image:IBH_Link_UA_Mitsubishi_Opening_Method.png|905px]] | |||
| Line 10: | Line 16: | ||
<br /> | <br /> | ||
<br /> | <br /> | ||
Within the IBH OPC UA Editor a new Mitsubishi configuration is added: | |||
[[Image: | [[Image:IBH_Link_UA_Add_Mitsubishi_Configuration.png|426px]] | ||
[[Image: | [[Image:IBH_Link_UA_Mitsubishi_New_Station.png|332px]] | ||
<br /> | <br /> | ||
<br /> | <br /> | ||
As next step the appropriate CPU is created: | |||
[[Image: | [[Image:IBH_Link_UA_Mitsubishi_New_CPU.png|305px]] | ||
[[Image: | [[Image:IBH_Link_UA_Mitsubishi_FX_CPU.png|347px]] | ||
<br /> | <br /> | ||
<br /> | <br /> | ||
To create variables, a structure must be defined: | |||
[[Image:IBH_Link_UA_Mitsubishi_New_Structure.png|237px]] | |||
[[Image: | [[Image:IBH_Link_UA_Mitsubishi_Structure.png|482px]] | ||
Then the desired variables can be created: | |||
[[Image: | [[Image:IBH_Link_UA_Mitsubishi_Variable.png|392px]] | ||
Latest revision as of 13:56, 8 September 2026
For the Mitsubishi control to be accessible via OPC UA, the SLMP Connection module must be inserted with the GX Works configuration software:
The settings for Opening Method must be set to Do not Open by Program.
Please note that these settings Opening Method are only available for the iQ-R series (and the older System Q). On the FX5U, these parameters cannot be configured.
Within the IBH OPC UA Editor a new Mitsubishi configuration is added:
As next step the appropriate CPU is created:
To create variables, a structure must be defined:
Then the desired variables can be created: